Rockwell Automation FLEX 5000 I/O Module Fault Vulnerability in CIP Class 32 Handling

Vulnerability

A vulnerability exists in the Rockwell Automation FLEX 5000 I/O 5094-IY8 device due to improper management of requests related to CIP Class 32 when the module is inhibited. This mismanagement causes the module to enter a fault state, indicated by a flashing red LED. Once the module is un-inhibited, it returns a connection fault (Code 16#0010) and cannot recover without a power cycle.

Impact

The vulnerability causes the affected module to enter a fault state, with the Module LED flashing red. After being un-inhibited, the module experiences a connection fault (Code 16#0010) and requires a power cycle to recover.

Remediation

Users should update to version 2.012 or later. If an upgrade is not possible, security best practices should be applied.

Added: Aug 14, 2025, 3:43 PM
Updated: Aug 14, 2025, 3:43 PM

Vulnerability Rating

Custom Algorithm
spread
0.0
impact
2.5
exploitability
7.4
remediation
7.7
relevance
0.4
threat
0.0
urgency
2.9
incentive
5.8

Our algorithm analyzes dozens of metrics to generate these 8 key vulnerability categories, which are then combined to calculate the overall risk score.